SKJ-4RD Feed-through terminal blocks integrates fuse function, effectively protecting the circuit from overload and short circuit damage. Its compact design and easy installation make it suitable for various electrical equipment that require fuse protection, such as motor control, power distribution, etc.
lntroduction
>>SKJ-4RD/X, 4RD, 2.5RD/X, 2.5RD are the disconnected rotating arm type fuse test terminal, the rotating arm can be opened upside, and fixed on final position, fuse can be installed inside rotating arm, these terminals can provide light indicator or without.
>>SKJ-10RD, 10RD/X are screw cap type fuse terminal, fuse can be 5X20mm, 5X25mm, bridged by used of central jumper SFBl 10-12, two kinds of model: with or without light indicator, the one with indicator will light if fuse blown down.
>>Notices: the terminal shall be chosen according to maxi power consumption of fuse (itself temper-ature). Check heating status of fuse terminal based application and mounting modes, at that case of higher temperature, it may give extra burden to fuse, if so, please consider regulating (reducing) rated working current.
Order No. | 01020 | |||
Dimensions | ||||
Width x Length x Height | (mm) | 72.5/8.2/56 | ||
Nominal screw diameter | (mm) | M3 | ||
Torque | (Nm) | 0.5-0.8 | ||
Stripping Length | (mm) | 8 | ||
Parameter | ||||
Voltage Rating | (V) | 800 | ||
Current Rating | (A) | 6.3 | ||
Wire section | (mm²) | 4 | ||
Wire Range | ||||
Rigidity wire range | (mm²) | 0.2-4 | ||
Soft wire range | (mm²) | 0.2-4 | ||
DIN Rails | Type | Order No. | ||
Mountable rail type | G32-15L G32-18/15 |
02006 02007 |
||
TH35-7.5 | 02005 | |||
End clapboard | ||||
SKJ-2.5RDG | 01080 | |||
Clapboard | ||||
For electric separation of neighboring bridges, can be fitted later, no loss of pitch. |
||||
Compensation room clapboard | ||||
Laid out with common terminal, compen sating for the staggered space. |
||||
Internal Jupmer | ||||
Used for transversely bridge conn- ected in the center of terminal block, according to actual operation the voltage can be distributed. |
10 pole | |||
3 pole | ||||
2 pole | ||||
External Jumper | ||||
2 pole | ||||
3 pole | ||||
10 pole | ||||
Mark Tag | ||||
Blank | SZB8-10 | 01066 | ||
10 no. Horz. | SZB8 (Horizontal) | |||
10 no. Vert. | SZB8 (Vertical) | |||
G Fuse type 5×20 | 01069 |
PREV
Clean Our Workshop
NEXT
NULL
GET A QUOTE